ASSE Standard #1002-2008
Performance Requirements for Anti-Siphon Fill Valves for Water Closet Tanks
Provides dimensional and minimum performance requirements for anti-siphon
fill valves for water closet tanks, including protection of the potable
water supply against back siphonage of water from the water closet tank.
Order here
ASSE
Standard #1003-2001
Performance Requirements for Water Pressure Reducing Valves
ANSI Approved - 2001
Devices covered by this standard are self-contained, direct acting, single
diaphragm types. Devices shall be permitted to have an integral strainer,
separate strainer connected to the valve inlet, or be without strainer.
Devices shall be permitted to be with or without an integral bypass relief
valve. The purpose of this device is to reduce static and flowing pressures
in water distribution systems.
Order here
ASSE Standard #1004-2008
Backflow Prevention Requirements for Commercial
Dishwashing Machines
Applies to the backflow prevention device used on the potable water supply
connected to a commercial dishwashing machine.
Order here
ASSE Standard
#1006-1986
Performance Requirements for Residential Use Dishwashers
Applies to residential use (household) type dishwashers, both front loading
and top loading, requiring connection to the potable water supply and
discharging into the plumbing drainage system.
Order here
ASSE Standard #1007-1986
Performance Requirements for Home Laundry
Equipment
Applies to household type automatic and semiautomatic clothes washers,
combination washer-dryers, and dryers including those household types that
are coin-operated, requiring connection to the potable water supply and
discharging into the building plumbing drainage system.
Order here
ASSE
Standard #1008-2006
Performance Requirements for Plumbing Aspects of Residential Food Waste
Disposer Units
ANSI Approved - 2006
Applies to the plumbing aspects of residential food waste disposers intended
for installation in the residential kitchen sink outlet, which when supplied
with water from the sink supply faucet discharge into the sanitary drainage
system.
Order here
ASSE Standard #1009-1990
Performance Requirements for Commercial Food Waste
Grinder Units
Applies to food waste grinders
designed and intended for use in food establishments, supplied with water
and which discharges waste into a plumbing drainage system.
Order here
ASSE
Standard #1010-2004
Performance
Requirements for Water Hammer Arresters
ANSI Approved - 2004
Applies only to those devices classified as water hammer arresters having a
permanently sealed cushion of water or gas isolated from the waterway, and
designed to provide continuous protection, without maintenance, against
detrimental surge pressures within the water distribution system. Water
hammer arresters are installed on water distribution system piping to
prevent over pressures within water distribution systems, thereby prolonging
the service life of valves, piping, fittings, trim, equipment, appliances,
appurtenances, and other devices which are part of the distribution system;
and to eliminate noise.
Order here
ASSE Standard #1011-2004
Performance Requirements for Hose Connection Vacuum Breakers
ANSI Approved - 2004
Applies only to those devices classified as Vacuum Breakers, Hose Connection
Type, which are designed to be installed on the discharge side of the hose
bibb, hydrant or faucet which is fitted with hose threads. The design
embraces a check valve member force loaded, or biased, to a closed position,
and an atmospheric vent valve, force loaded, or biased, to an open position
when the device is not under pressure. This device shall not be subjected to
continuous pressure. Continuous pressure shall mean twelve (12) hours use in
a twenty-four (24) hour period. Mechanical means used to defeat the vacuum
breaker shall not be used. This device shall only be used on systems where
the only source of low head back pressure comes from an elevated hose equal
to or less than three (3.0) meters (10 feet) in height.
Order here
ASSE Standard #1012-2002
Performance Requirements for Backflow Preventer with Intermediate
Atmospheric Vent
ANSI Approved - 2002
The devices covered by this standard are those which have functional
capabilities for preventing both backsiphonage and back pressure backflow in
the potable water supply lines, and which can operate under continuous or
intermittent pressure conditions. These devices have two independently
operating check valves separated by an intermediate chamber with a means for
automatically venting it to the atmosphere. The check valves are force
loaded to a normally closed position and the venting means is force loaded
to a normally open position.
Order here
ASSE Standard #1013-2005
Performance Requirements for Reduced Pressure Principle Backflow Preventers
and Reduced Pressure Fire Protection Principle Backflow Preventers
ANSI Approved - 2005
Applies only to two types of backflow prevention assemblies identified as
(RP) “Reduced Pressure Principle Backflow Preventers” and (RPF) “Reduced
Pressure Principle Fire Protection Backflow Preventers.” These assemblies
consist of two (2) independently-acting check valves, internally force
loaded to a normally closed position, and separated by an intermediate
chamber (or zone) in which there is an hydraulically operated relief means
for venting to atmosphere, internally force loaded to a normally open
position. These assemblies are designed to operate under continuous pressure
conditions. The assembly shall include two (2) tightly closing shut-off
valves, and contain properly located test cocks. This standard also applies
to Manifold Reduced Pressure Principle Backflow Assemblies. They consist of
two or more complete Reduced Pressure Principle Backflow Preventers in
parallel. The assemblies do not need to be of the same pipe size. The
manifold size shall be identified by the single inlet and outlet of the
manifold reduced pressure principal backflow assembly. It shall consist of
shut-off valves on the inlet and outlet of each of the assemblies in the
manifold and the shut-off valves shall be line sized to each backflow
assembly in the manifold.
Order here
ASSE Standard #1014-2005
Performance Requirements for Backflow Prevention Devices for Hand-Held
Showers
ANSI Approved - 2005
Provides performance requirements for backflow prevention device(s) for
hand-held showers in the interest of health and safety. These devices
provide backflow protection against backsiphonage and backpressure in
hand-held showers. These are separate devices or are integral with
wall-mounted or deck-mounted tub fillers, flexible hoses, or components that
are attached to shower arms.
Order
here
ASSE Standard #1015-2005
Performance Requirements for Double Check Backflow Prevention Assemblies and
Double Check Fire Protection Backflow Prevention Assemblies
ANSI Approved - 2005
Applies to two types of backflow prevention assemblies identified as a
(Double Check Backflow Prevention Assembly (DC) and a Double Check Fire
Protection Backflow Prevention Assembly (DCF). These assemblies consist of
two (2) independently acting check valves, internally force loaded to a
normally closed position, two (2) tightly closing shut-off (isolation)
valves, and properly located test cocks. These assemblies are designed and
constructed to operate under intermittent or continuous pressure conditions.
This standard also applies to Manifold Double Check Backflow Prevention
Assemblies. These consist of two or more complete Double Check Backflow
Prevention Assemblies in parallel.
Order here
ASSE Standard #1016-2005
Performance Requirements for Automatic Compensating Valves for Individual
Showers and Tub/Shower Combinations
ANSI Approved - 2005
Automatic Compensating Valves for Individual Showers and Tub/Shower
Combinations are intended to control the water temperature to wall mounted
shower heads either in individual shower or tub/shower combination fixtures
in order to reduce the risk of scalding and thermal shock. These devices are
intended to be installed at the point-of-use, where the bather or bather’s
attendant has access to flow and final temperature control mechanisms, and
where no further mixing occurs downstream of the device. The three (3) types
of individual control valves covered by this standard are: 1. Pressure
balancing valves (Type P) have a mechanism that senses incoming hot and cold
water pressures and compensates for fluctuations in either to stabilize
outlet temperature. 2. Thermostatic valves (Type T) have a mechanism that
senses outlet temperature and compensates for fluctuations in either
incoming hot and cold water temperature and/or pressure to stabilize outlet
temperature. 3. Combination thermostatic/pressure balancing valves (Type
T/P) sense outlet temperature and incoming hot and cold water pressures and
compensates for fluctuations in incoming hot and cold water temperatures
and/or pressures to stabilize the outlet temperature. These devices are
intended to be the final temperature control.
Order here
ASSE Standard #1017-2003
Performance Requirements for Temperature Actuated Mixing Valves for Hot
Water Distribution Systems
Temperature Actuated Mixing
Valves for Hot Water Distribution Systems are used for controlling in-line
water temperatures in domestic potable hot water systems and shall be
installed at the hot water source. They are not intended for end use
application. Temperature Actuated Mixing Valves for Hot Water Distribution
Systems shall consist of a hot water inlet connection, a cold water inlet
connection and a mixed water outlet connection plus a temperature sensing
and controlling element and a means for adjusting the outlet water
temperature.
Order here
ASSE Standard #1018-2001
Performance Requirements for Trap Seal Primer Valves - Potable Water
Supplied
ANSI Approved - 2002
Devices covered by this standard are designed primarily to supply water to
drain traps which have infrequent use and in which water evaporation would
allow sewer gas to enter the premises. This type of device is located in the
domestic water distribution system and is designed to supply potable water
to a drain trap to maintain the water seal. A means for the prevention of
backsiphonage shall be incorporated as part of the device.
Order here
ASSE Standard #1019-2004
Performance Requirements for Vacuum Breaker Wall Hydrants, Freeze Resistant,
Automatic Draining Type
ANSI Approved - 2004
The purpose of these devices is to supply potable water without danger of
damage to the device due to freezing; and to provide protection of the
potable water supply from contamination due to back siphonage or back
pressure less than or equal to 3 meters (10 feet) of head pressure. This
standard covers design and performance requirements for water supply system
wall hydrant devices. These devices shall have a permanent means including
air inlet valve(s) to prevent backflow from a potential health hazard due to
back siphonage, and back pressure less than 3 meters (10 feet) of head
pressure. The device shall only be used on systems where the only source of
back pressure comes from an elevated hose equal to or less than 3 meters (10
feet) in height and from full rated supply pressure. The devices shall be
classified as follows: (a) Type A: These hydrants automatically drain the
water when the water supply is shut off and the hose removed to prevent
damage from freezing; (b) Type B: These hydrants automatically drain the
water with a hose removed or attached, end nozzle closed, and the hydrant
valve closed; and (c) Type C: Same as Type A. Backflow prevention is
achieved by alternate principle of holding pressure versus relieving
pressure.
Order here
ASSE Standard #1020-2004
Performance Requirements for Pressure Vacuum Breaker Assembly
ANSI Approved - 2004
Pressure vacuum breaker assemblies are for installation in water supply
lines to prevent the entrance of non-potable material into the potable water
supply by backsiphonage only. It is not for use in any system where
backpressure can be applied to the assembly. When a supply pressure is
between 7 to 14 kPa (1 to 2 p.s.i.), the air inlet valve is open and the
assembly will continuously discharge. Due to this probability of water
discharge from the atmospheric air inlet valve, the assembly shall only be
installed where water discharge does not cause damage.
Order here
ASSE Standard #1021-2001
Performance Requirements for Drain Air Gaps for Domestic Dishwasher
Applications
ANSI Approval Pending
Products covered by the standard are devices for installation in the drain
line of residential dishwashers. The purpose of this device is to prevent
the backflow of contaminated liquid and entrained material into the
dishwasher.
Order here
ASSE Standard #1022-2003
Performance Requirements for Backflow Preventer for Beverage Dispensing
Equipment
ANSI Approved - 2003
Covers a backflow prevention
device designed to protect the potable water supply serving beverage
dispensing equipment. These devices are intended for use under continuous or
intermittent pressure conditions. They shall consist of two independently
acting check valves biased to a normally closed position. An atmospheric
port shall be located between the check valves and shall be biased to a
normally open position. The port shall vent liquids, gases, or both, under
backflow conditions.
Order here
ASSE Standard #1023-1979
Performance Requirements for Hot Water Dispensers Household Storage Type -
Electrical
The hot water dispensers covered
by this standard are those which are designed for household use and which
are installed at the sink and supplied with water from the kitchen sink
water supply. They are storage types, continuously vented to atmosphere and
heated electrically.
Order here
ASSE Standard #1024-2004
Performance Requirements for Dual Check Backflow Preventers
ANSI Approved - 2004
Applies only to the type of backflow preventer identified as a dual check
backflow preventer. This device
consists of two (2) independently acting check valves, internally force
loaded to a normally closed position, designed and constructed to operate
under intermittent or continuous pressure conditions. The purpose of the
dual check backflow preventer is to keep polluted water from flowing back
into the potable water system, when pressure is temporarily higher in the
polluted part of the system than in the potable water piping. The devices
covered by this standard are intended to protect the potable water supply
from low hazard pollution at residential service lines and individual
outlets. These devices are intended for cold water service under continuous
or intermittent pressure conditions. Usage with hot water is limited to the
temperature specified by the manufacturer.
Order here
ASSE Standard #1032-2004
Performance Requirements for Dual Check Valve Type Backflow Preventers For
Carbonated Beverage Dispensers - Post Mix Type
The devices covered by this standard are those with functional capabilities
for preventing back pressure backflow in water supply lines, and which can
operate under continuous or intermittent pressure conditions. These devices
consist of two independently acting primary check valves, internally force
loaded to a normally closed position, in a common casing or valve body.
Devices may have a supplementary check valve downstream of the primary
downstream check valve. Where it is incorporated in the design, it shall be
held open by suitable means or removed for all performance tests where
noted.
Order here
ASSE Standard #1035-2008
Performance Requirements for Laboratory Faucet Backflow Preventers
Laboratory Faucet Backflow Preventers are designed to protect the potable
water supply from pollutants or contaminants which enter the system by
backflow due to back siphonage or back pressure. This standard applies only
to those devices classified as backflow preventers that are designed for
installation on laboratory faucets on the discharge side of the last
shut-off valve. These devices are not for use under constant pressure
conditions. These devices consist of two independently acting check valves,
force loaded or biased to a normally closed position, and between the check
valves a means for automatically venting to atmosphere, force loaded or
biased to normally open position.
Order here
ASSE Standard #1037-1990
Performance Requirements for Pressurized Flushing Devices (Flushometers) for
Plumbing Fixtures
Establishes basic performance requirements for pressurized flushing devices,
for the safe and sanitary operation of plumbing fixtures.
Order here
ASSE Standard #1043-1992
Performance Requirements for Cast Iron Sovent Sanitary Drainage Systems
Establishes functional performance
requirements for cast iron sovent drainage fittings, aerators and deaerators,
and installation guidelines for the system. A cast iron sovent system is a
single-stack drainage, waste and vent system that uses special fittings
(aerators and deaerators) to maintain the differential pressures within the
system near atmosphere, thereby protecting the trap seals of the connected
fixtures.
Order here
ASSE Standard #1044-2001
Performance
Requirements for Trap Seal Primer Devices - Drainage Types and Electronic
Design Types
ANSI Approved - 2002
Devices covered by this performance standard are designed primarily to
supply water to floor drain traps which have infrequent use and in which
water evaporation would allow sewer gas to enter the premises. The type of
device covered by this standard is designed to supply water to a drain trap
to provide and maintain its water seal using a supply from a fixture
drainline, ballcock, or flushometer valve tailpiece or an electronic primer
device. The rate of water flow to the trap shall be permitted to be fixed or
adjustable. The devices are of four (4) types: (a) Those which are installed
on waste line tail pieces from fixtures, such as lavatories, sinks and
similar fixtures where grease is not normally generated; (b) Those which are
used in conjunction with ballcock assemblies; (c) Those which receive flow
from flushometer valves; and (d) Those electronics devices which discharge
water automatically and which are upstream of the air gap or vacuum breaker.
Order here
ASSE Standard #1047-2005
Performance Requirements for Reduced Pressure Detector Fire Protection
Backflow Prevention Assemblies
ANSI Approved - 2005
Applies to the type of assembly identified as Reduced Pressure Detector Fire
Protection Backflow Prevention Assemblies (RPDF). This assembly consists of
two (2) independently-acting check valves, internally force loaded to a
normally closed position, and separated by an intermediate chamber (or zone)
in which there is a hydraulically operated relief means for venting to
atmosphere, internally force loaded to a normally open position. These
assemblies are designed to operate under continuous pressure conditions.
This standard also applies to Manifold Reduced Pressure Fire Protection
Backflow Prevention Assemblies. They consist of two or more complete RPDF
assemblies in parallel. The assemblies do not need to be of the same pipe
size.
Order here
ASSE Standard #1048-2005
Performance Requirements for Double Check Detector Fire Protection Backflow
Prevention Assemblies
ANSI Approved - 2005
Applies to the type of backflow prevention assembly identified as Double
Check Detector Fire Protection (DCDF). These assemblies consist of two (2)
independently-acting check valves, internally force loaded to a normally
closed position. These assemblies are designed to operate under continuous
pressure conditions. This standard also applies to Manifold DCDF assemblies.
They consist of two (2) or more complete DCDF assemblies in parallel. The
assemblies do not need to be of the same pipe size. The manifold size shall
be identified by the single inlet and outlet of the manifold DCDF assembly.
It shall consist of shut-off valves on the inlet and outlet of each of the
assemblies in the manifold and the shut-off valves shall be line sized to
each DCDF assembly in the manifold.
Order here
ASSE Standard #1050-2002
Performance Requirements for Stack Air Admittance Valves for Sanitary
Drainage Systems
ANSI Approval Pending
Stack Air Admittance Valves for Sanitary Drainage Systems are used as vent
terminals for stacks in plumbing drainage systems. These devices shall not
be used to relieve back pressure, but only to allow air to enter the system.
When these devices are installed in a building, there shall be at least one
(1) open vent terminal which extends to atmosphere outside of the building
serving the building drain on which these devices are installed. These
devices are designed to be installed on stacks where branches on multiple
floors are connected. These devices consist of a one-way valve designed to
allow air to enter the plumbing drainage system when a pressure less than
atmospheric develops. The device closes and seals by gravity under zero (0)
differential pressure (static or no flow condition) and under positive
pressure. These devices prevent sewer gases from entering a building. The
device consists of a hooded or shielded body which contains a movable guided
diaphragm which seats and seals air flow when closed and allows air to enter
when open.
Order here
ASSE Standard #1051-2002
Performance Requirements for Individual and Branch Type Air Admittance
Valves for Sanitary Drainage Systems
ANSI Approval Pending
Individual and Branch Type Air Admittance
Valves for Sanitary Drainage Systems (AAV’s) are used as vent terminals for
individual and branch fixtures in plumbing drainage systems. These devices
shall not be used to relieve back pressure, but only to allow air to enter
the system. When the devices are installed in a building, there shall be at
least one (1) open vent terminal which extends to atmosphere outside of the
building serving the same building drain on which these devices are
installed. These devices are designed to be used for individual fixtures or
for a branch serving multiple fixtures. These devices consist of a one-way
valve designed to allow air to enter the plumbing drainage system when a
pressure less than atmospheric develops. The device closes and seals by
gravity under positive pressure. These devices prevent sewer gases from
entering the building. The device consists of a hooded or shielded body
which contains a movable guided diaphragm which seats and seals air flow
when closed and allows air to enter when open.
Order here
ASSE Standard #1052-2004
Performance Requirements for Hose Connection Backflow Preventers
ANSI Approved - 2004
Establishes physical requirements, basic performance requirements and test
procedures for hose connection backflow preventers. This device is designed
to be installed on the discharge side of a hose threaded outlet on a potable
water system. This two-check device protects against backflow, due to
backsiphonage and low-head backpressure, under the high hazard conditions
present at a hose threaded outlet. This device shall only be used on systems
where sources of backpressure are not introduced. This device shall only be
used on systems where the low-head backpressure does not exceed that
generated by an elevated hose equal to or less than 3 m (10 ft.) in height.
This device shall not be subjected to more than twelve (12) hours of
continuous water pressure. A hose connection backflow preventer shall
consist of two independent checks, force loaded or biased to a closed
position, with an atmospheric vent located between the two check valves,
which is force loaded or biased to an open position, and a means for
attaching a hose.
Order here
ASSE Standard #1053-2004
Performance Requirements for Dual Check Backflow Preventer Wall Hydrants -
Freeze Resistant Type
Establishes design and performance requirements and test procedures for Dual
Check Backflow Preventer Wall Hydrants - Freeze Resistant. The purpose of
these devices is to provide protection of the potable water supply from
contamination due to backsiphonage or backpressure without damage to the
device due to freezing, and is field testable to verify protection under the
high hazard conditions present at a hose threaded outlet. This device shall
only be used on systems where the low-head backpressure does not exceed that
generated by an elevated hose equal to or less than 10.0 feet (3.0 m) in
height, and are not subjected to continuous water pressure.
Order here
ASSE
Standard #1055-1997
Performance Requirements for Chemical Dispensing Systems
Chemical dispensing systems
provide a means of mixing potable water with chemicals to provide the user
with a chemical solution which is ready for use. The amount of dilution
shall be fixed or adjustable. This standard applies to those devices
classified as chemical dispensing systems having self- contained means of
backflow protection. The devices shall be classified as follows: (a) Type A:
These devices have the chemical(s) pressurized above atmospheric pressure;
and (b) Type B: These devices do not pressurize the chemical(s) above
atmospheric pressure with the only source of back pressure coming form an
elevated hose.
Order here
ASSE Standard #1056-2001
Performance Requirements for Spill Resistant Vacuum Breaker
ANSI Approved - 2002
Spill Resistant Vacuum Breakers are installed in the potable water supply
lines to prevent the backflow or nonpotable material into the potable water
supply caused by backsiphonage only. They are not for use in any system
where back pressure is applied to the device. When the system is
pressurized, the vent closes to prevent a flow through the upstream check
valve, and to eliminate vent spillage. This standard applies only to those
devices classified as Spill Resistant Vacuum Breakers - SVB. These devices
are designed for installation in those portions of the domestic potable
water systems that are normally under continuous pressure conditions. The
device includes one (1) check valve force-loaded closed and an air inlet
vent valve force loaded open to atmosphere, positioned downstream of the
check valve, and located between and including two (2) tightly closing
shut-off valves and two (2) test cocks.
Order here
ASSE Standard #1057-2001
Performance Requirements for Freeze Resistant Sanitary Yard Hydrant with
Backflow Protection
ANSI Approval Pending
The purpose of freeze resistant sanitary yard hydrants is to supply potable
water without danger of damage to the hydrant due to freezing, to provide
protection of the potable water supply from contamination due to ground
water, and to prevent backflow in accordance with the backflow prevention
device selected. These devices shall only be used on systems where the
low-head backpressure does not exceed that generated by an elevated hose
equal to or less than 3 m (10 ft. ) in height. This device shall not be
subjected to continuous pressure.
Order here
ASSE Standard #1060-2006
Performance Requirements for Outdoor Enclosures for
Fluid Conveying Components
ANSI Approved - 2006
Focuses on devices that provide a range of protection for fluid conveying
components which are mounted outside & above ground so that they may avoid
damage from freezing, vandalism & tampering. Fluid conveying components
include backflow prevention assemblies & devices, water meters, control
valves, pressure reducing valves, air release valves, pumps & other
components installed outdoors & above ground that require protection from
freezing or require system security protection.
Order here
ASSE Standard #1061-2006
Performance Requirements for Removable & Non-Removable Push-Fit Fittings
ANSI Approved - 2006
Applies to push-fit fittings than can be used with one or more of the
following materials:
1) PEX tubing complying with ASTM F 876 or ASTM F 877;
2) Type K, L and M copper tubing complying with ASTM B 88; and
3) CPVC tubing complying with ASTM D 2846.
Push-fit fittings may be designed to be used with one or more types of
tubing that conform to the dimensions as specified in their respective
standard. This standard serves to supplement ASTM F 877, ASTM D 2846 & ASTM
B88 in describing a test method for a specific type of push-fit fitting
system to be used with PEX, Copper &/or CPVC tubing. This standard covers
minimum requirements for materials of construction & prescribes minimum
performance requirements for fitting joints, marking & identification.
Order here
ASSE Standard #1062-2006
Performance Requirements for Temperature Actuated, Flow Reduction (TAFR)
Valves for Individual Fixture Fittings
ANSI Approved - 2006
Applies to Temperature Actuated, Flow Reduction (TAFR) Valves for Individual
Supply Fittings which react to high temperature water. These valves are
intended for use in-line with or are integrated into individual plumbing
supply fittings such as shower heads, bath and utility faucets and sink and
lavatory faucets. These devices shall automatically reduce flow within five
(5) seconds to 0.25 GPM (0.95 L/m) or less at 80 psi (551.6 kPa) in response
to outlet temperatures greater than a preset actuation temperature not to
exceed 120 °F (48.9 °C) so as to limit exposure to high temperature water
discharged from an individual supply fitting.
Order here
ASSE Standard #1063-2008
Performance Requirements for Air Valve & Vent Intake Preventers
The purpose of Air Valve and Vent
Inflow Preventer Assemblies is to allow the release and admission of high
volumes of air through air valves and air vents in water distribution
systems but prevent the entry of contaminated water when the air valve
outlet becomes submerged from flooding or is the target of malicious
tampering.
This assembly shall
consist of a primary and a secondary chamber. Each chamber shall contain an
independent float-operated closure member. The primary chamber is the lower
chamber. The secondary or upper chamber is redundant and will close in the
event the primary chamber fails to close.
Order here
ASSE Standard #1064-2006
Performance Requirements for Backflow Prevention Assembly Field Test Kits
ANSI Approved - 2006
Portable backflow prevention assembly field test kits (BFTK) shall be used
in testing the performance of backflow prevention assemblies. This standard
covers the performance requirements, and accuracy of a BFTK. This standard
is confined to analog dial type and digital instrumentation. Duplex gauges
are not a part of this standard. They shall be designed to indicate the
operation of a backflow prevention assembly to pre-established testing
procedures. The backflow field test kit shall include all gauges, hoses,
valves and fittings as required for testing purposes.
Order here
ASSE Standard #1066-1997
Performance Requirements for Individual Pressure Balancing In-Line Valves
for Individual Fixture Fittings
Applies to automatic pressure balancing in-line valves which are used to
equalize incoming hot and cold water line pressures for the purpose of
minimizing mixed water temperature variations due to pressure fluctuations
when used in conjunction with a mixing valve or two handle valve set. They
are not designed to limit the maximum outlet temperature at the
point-of-use. These devices are intended for use in individual plumbing
fixtures fittings such as shower heads, bath utility
faucets, and sink and lavatory faucets.
Order here
ASSE Standard #1069-2005
Performance Requirements for Automatic Temperature Control Mixing Valves
ANSI Approved - 2005
These devices shall be designed to supply only tempered water to the end
user, and automatically compensate for pressure and/or temperature
variations in water distribution systems. These devices shall have the
capability to significantly reduce the outlet flow in the event of a cold
water distribution system failure. The device shall be equipped with an
adjustable means to limit the setting of the device towards the hot
position. The device is designed to be the final temperature control.
Order here
ASSE Standard #1070-2004
Performance Requirements for Water Temperature Limiting Devices
ANSI Approved - 2004
Water Temperature Limiting Devices shall control and limit the water
temperature to fittings for fixtures such as sinks, lavatories or bathtubs
and are intended to reduce the risk of scalding. These devices are intended
to supply tempered water to plumbing fixture fittings, or be integral with
plumbing fixture fittings supplying tempered water. The device shall be
equipped with an adjustable and lockable means to limit the setting of the
device towards the hot position. Where the device is integral to the fixture
fitting, it shall comply with the requirements of ASME A112.18.1.
Order here
ASSE Standard #1071-2008
Performance Requirements for Temperature Actuated Mixing Valves for Plumbed
Emergency Equipment
Water mixing (also defined as tempering or blending) valves are used
extensively in applications for emergency shower/eye and face wash systems
to mix hot and cold water to provide "tepid" water. The term "tepid" has not
been specifically defined, but is generally understood to mean "lukewarm" or
"moderately warm". Valves designed to meet this standard are intended to be
used as a component that can provide tepid water for emergency eye wash and
shower equipment that comply with the requirements of ANSI Standard Z358.1.
Order here
ASSE Standard #1072-2007
Performance Requirements for Barrier Type Floor Drain Trap Seal Protection
Devices
This new ASSE Standard #1072 introduces an alternative method of protecting
floor drain water trap seals- Barrier-Type Floor Drain Trap Seal Devices.
Because this barrier method does not automatically and periodically provide
water to replenish the trap seal, it must provide a barrier on the inlet
side of the trap seal that will minimize its evaporation caused by the
ambient air on the building side of the trap. This barrier must also provide
adequate drainage capabilities required for the floor drain’s intended use
as determined by its design, size, and installation location.
While developing
the performance requirements and tests for these devices, certain adverse
conditions were taken into consideration. These are the introduction of
fouling substances such as dirt/sand, floor wax or grease directly into the
device. In addition drainage requirements to accommodate infrequent, and
unusually sizeable, water flows caused by water line breaks, fixture
overflows or backflow preventer discharges are provided. Tests are included
to confirm that devices submitted for approval provide the performance
requirements listed above- among others.
Order here
ASSE Standard #1079-2005
Performance Requirements for Dielectric Pipe Unions
Dielectric pipe unions are designed to prevent stray current in piping
systems. These stray currents can come from dissimilar piping materials or
improper grounding of electrical equipment. This standard provides guidance
in the construction of pipe unions that incorporate electrical insulating
properties to reduce the accelerated corrosion that can result from galvanic
and stray currents.
Order here
ASSE SERIES 5000-2004
Professional Qualifications Standard for Backflow
Prevention Assemblies Testers, Repairers and Surveyors
Applies to any field inspection performance requirement used to
appraise the performance of:
• Reduced Pressure Principle Backflow Preventers and Reduced Pressure Fire
Protection Principle Backflow Preventers (ASSE 1013)
• Double Check Backflow Prevention Assemblies and Double Check Fire
Protection Backflow Prevention Assemblies (ASSE 1015)
• Pressure Vacuum Breaker Assembly (ASSE 1020)
• Reduced Pressure Detector Fire Protection Backflow Prevention Assembly
(ASSE 1047)
• Double Check Detector Fire Protection Backflow Prevention Assemblies (ASSE
1048)
• Hose Connection Backflow Preventer (ASSE 1052)
• Spill Resistant Vacuum Breaker (ASSE 1056)
Also applies to any individual who is certified in accordance
with this standard and who will:
• Test all types of backflow preventers
• Perform a cross-connection control survey inspection
• Repair all approved backflow preventers.
Order here
SERIES 6000-2006
Professional Qualifications Standard for Medical Gas Systems Personnel
ANSI Approved -
2006
6005 - Medical Gas Systems
Specialist
Provides general knowledge of medical gas and vacuum systems for the purpose
of providing continuing education. Eligible individuals include any person
with an interest in medical gas and vacuum systems and equipment.
6010 - Medical Gas Systems
Installers
Applies to any individual who installs medical gas and vacuum systems.
Installers include anyone who works on or installs piping or components,
including brazers.
6015 - Bulk Medical Gas Systems
Installers
Applies to any individual who installs bulk systems for medical gas at
health care facilities. Installers include anyone who works on or installs
bulk systems or bulk system components, including brazers on bulk supply
systems.
6020 - Medical Gas Systems
Inspectors
Applies to any individual who inspects the installation of medical gas and
vacuum distribution pipeline systems.
6030 - Medical Gas Systems
Verifiers
Applies to any individual who tests and verifies the operation of medical
gas and vacuum systems.
6040 - Medical Gas Systems
Maintenance Personnel
Applies to any individual who maintains medical gas and vacuum systems.
6050 - Medical Gas Systems
Instructors
Applies to any individual who trains or teaches installers, inspectors,
verifiers and healthcare facility maintenance personnel regarding medical
gas and vacuum distribution systems.
6055 - Bulk Medical Gas Systems
Instructors
Applies to any individual who trains or teaches bulk system installers.
Order here